ONLINE IDENTIFICATION OF POWER SYSTEM DOMINANT EIGENVALUES BASED ON ZERO-INPUT RESPONSES FOLLOWING LIMITED-TIME DISTURBANCES

XIAO Jin-yu,XIE Xiao-rong,HAN Ying-duo
DOI: https://doi.org/10.3321/j.issn:0258-8013.2005.12.001
2005-01-01
Abstract:Studying the distribution of dominanteigenvalues of the linearized system is an important approach toanalyzing small-signal stability of large-scale power systems.The characteristic of identifying eigenvalues of linear systembased on zero-input response is analyzed, and then theidentifiability is represented. This paper proposes a new methodfor online identifying the distribution of dominant eigenvalues.With the improved Prony algorithm, multi-channel outputresponses, which are measured at different sites followingcertain finite-duration disturbance, are approximated withProny signal-models. Thus the dominant eigenvalues of thestudied power systems are obtained. The proposed methodovercomes the drawback of conventional off-line small-signalanalysis, which is of low reliability because of variation ofoperating condition and uncertainties in model parameters.Based on the real-time data platform of industrializedWide-Area Measurement System (WAMS), the framework andflow for online monitoring eigenvalues of power grid isrepresented. Simulation results and field test data validate itsthe effectiveness.
What problem does this paper attempt to address?