High Impedance Fault Detection on Distribution Systems with Harmonic Interference in Wind Farms

Jiang Ni,Bin Wang,Xinzhou Dong
DOI: https://doi.org/10.1049/cp.2016.0123
2016-01-01
Abstract:High impedance faults (HIFs) are easy to occur in collective feeders in wind farms and may cause the cascading of wind generators tripping. This kind of faults is difficult to be detected by traditional relay or fuse due to the limited fault current values and the situation is worse in wind farms. The mostly adopted HIF detection algorithms are based on the 3rd harmonic characteristic of the fault zero-sequence currents, whereas these 3rd harmonics are very easy to be polluted by wind power back-to-back converters. To solve this problem, the typical HIF arc flash based on Mayr's arc model is first built, and the typical fault waveforms of HIF in wind farm are presented. Then the characteristics of high impedance faults are analysed to distinguish the occurrence of HIF from other harmonic interference. After that, the performance of the traditional harmonic based HIF detection algorithm is discussed, and a novel detection algorithm is presented to prevent harmonic interference influence in wind farms.