Performance Simulation of a Novel Solid Desiccant Heat Pump System in Energyplus

Y. Jiang,T. Ge,R. Wang
2012-01-01
Abstract:The variable refrigerant volume (VRV) air conditioning system usually needs to be operated with a ventilation system, since the VRV system cannot provide fresh air. The commonly used ventilation unit with the VRV system is the heat recovery ventilation (HRV) unit. In this study, a novel solid desiccant heat pump unit (DESICA) is proposed and performance of this unit is investigated by simulation, while a new type of high sensible heat VRV (HSHVRV) is developed. Mathematical model of DESICA is developed based on the generic dynamic building energy simulation software – EnergyPlus, while the model of HSHVRV is developed based on the standard VRV model. Energy consumption of joint DESICA and HSHVRV system (JDHVS) is compared with the energy consumption of joint HRV and standard VRV system (JHSVS) in an office building, while system performance is investigated in the meanwhile. It is found that the JDHVS can keep indoor humidity ratio at about 50% RH, resulting in a better indoor thermal comfort than JHSVS. Also, simulation results show that the energy-saving potential of the JDHVS system can achieve 20% in cooling conditions and 20% in heating conditions, compared with the JHSVS, respectively.
What problem does this paper attempt to address?