A Ventilator with Multiple Modes for Ventilation and Air Filtration

Facheng Li,Tengfei (Tim) Zhang,Shugang Wang
DOI: https://doi.org/10.26868/25222708.2019.210675
2020-01-01
Abstract:In event of haze and fog in some countries, the outdoor air is polluted and cannot be directly drawn into rooms for ventilation. A ventilator with air filtration is required. Because the outdoor particulate concentrations vary greatly with time, adopting the high efficiency particulate air (HEPA) filtration may not be optimal. This investigation proposed a ventilator with multiple modes of ventilation and air filtration. Different efficiency of air filters were installed into the natural and mechanical ventilation passages. The ventilation rate and indoor particle concentrations were modelled by the EnergyPlus and validated with the experimental data. Then the validated model was adopted to evaluate both indoor air quality and ventilation energy consumption in a hypothetical apartment located in five different climatic zones. Performance of the proposed ventilator and the market-available fresh air blower was compared. It was found that both the proposed ventilator and the fresh air blower were able to assure both indoor CO2 and PM2.5 concentrations within the acceptable level. The operating time of the HEPA filtration for the proposed ventilator was approximately 70% less than that of the fresh air blower and for the operating energy the ventilator was approximately 30% less.
What problem does this paper attempt to address?