Performance analysis of a novel on-off control method for concrete radiant floor

Xiangjian Xiang,Tao Zhang,Mingyang Wu,Xiaohua Liu
2017-01-01
Abstract:In order to take full advantages of the thermal inertia of heating terminal and reduce return water temperature when using concrete radiant floor combined with heating network,adopts a novel on-off control method.Running time of water valve in each period is constant,which equals to the replacement time of water in the buried pipe of concrete terminal.When valve closes,water in the buried pipe releases heat to the floor while water temperature decreases.Establishes a heat transfer calculation model of concrete radiant floor to explore the performance of the control method.Simulation and test results show that under different working conditions,the floor surface temperature and heating capacity remain stable and the return water temperature decreases significantly so that the energy utilization efficiency can be improved.
What problem does this paper attempt to address?