Contaminant Dispersion From An Area Source With Displacement Ventilation

GQ He,XD Yang,J Srebric
2003-01-01
Abstract:A study of contaminant dispersion from an area contaminant source with displacement ventilation is reported. A small office (5.16x3.65x2.26m) is studied with the whole floor surface as an emission source of trace gas (SF6) used as a marker for sources such as carpet volatile organic compounds (VOCs). The evaluation of the exposure and the mixing status in the room shows that a stratification height divides the office into two distinctive zones. In the lower zone, the concentration has a sharp gradient, while the upper zone is well mixed with almost uniform concentrations. The stratification height observed is lower than the breathing height, indicating that the personal exposure is similar to the exposure with a perfect mixing system. Computational fluid dynamics (CFD) simulation results for this office space agree well with the experimental data.
What problem does this paper attempt to address?