A Novel DC Chopper Topology for VSC-Based Offshore Wind Farm Connection
Bin Xu,Chong Gao,Jing Zhang,Jun Yang,Bing Xia,Zhiyuan He
DOI: https://doi.org/10.1109/tpel.2020.3015979
IF: 5.967
2021-03-01
IEEE Transactions on Power Electronics
Abstract:Sudden increases in the dc-link voltage, caused by ac grid side voltage drops, can lead to potential damage in the equipment. Therefore, dc choppers are widely used in offshore wind power links to absorb the excess energy and keep the voltage within safe margins. This article investigates the existing chopper topologies and summarizes their advantages and disadvantages. On this basis, a novel dc chopper topology with both centralized and distributed resistances is proposed. It is a combination of two mainstream chopper topologies and gives the flexibility to tradeoff among the pros and cons of them. In this way, the proposed topology achieves great electromagnetic interference performance, precise power control, and very small system disturbance. In addition, the maximum power dissipation of the distributed resistance is reduced by 75%. The switching frequency and the loss of insulated gate bipolar transistors (IGBTs) are also decreased. Finally, the claimed attributes of the proposed topology are verified by test and simulation.
engineering, electrical & electronic
What problem does this paper attempt to address?