Dielectric Properties of High Voltage XLPE Power Cables Taken from Service

H. M. Wang,S. C. Fang,Z. Z. Meng,P. X. Song,X. Li,M. Z. Zhu,X. H. Zhu,Y. Yu,B. X. Du
DOI: https://doi.org/10.1109/CEIDP47102.2019.9009889
2019-01-01
Abstract:Various experiments were conducted to find criteria for characterizing and evaluating the insulation performance and aging status of high voltage (HV) cross-linked polyethylene (XLPE) cables operated for a period of time. The objects included insulation samples obtained from 220 kV XLPE cables operated for two, five, nine, twelve years and a new cable. We tested the samples and measured their dielectric loss (tanδ), oxidative induction time (OIT) and AC breakdown voltage. The measurement of these parameters can be an effective method for aging state assessment of XLPE cables in service. Meanwhile, the breakdown voltage of XLPE cable insulation can give general information of cable aging, and it is simple, effective and suits engineering practices.
What problem does this paper attempt to address?