Abstract:Abstract Dissolved gas analysis (DGA) method is widely used to detect the incipient fault of power transformers. This paper presents a novel DGA method for power transformer fault diagnosis based on Harris-Hawks-optimization (HHO) algorithm optimized kernel extreme learning machine (KELM). The non-code ratios of the gases are used as the characterizing vector for the KELM model, and the Harris-Hawks-optimization (HHO) algorithm is introduced to optimize the KELM parameters, which promotes the fault diagnostic performance of KELM. Based on dataset collected from IEC TC 10, the fault diagnosis capability of the proposed method is validated by different characterizing vectors and is compared with conventional KELM and other optimized KELM. Moreover, the generalization ability of the proposed method is confirmed by China DGA data. The results demonstrate that the proposed method is superior to other methods and is more effective and stable for power transformer fault diagnosis with high accuracy.
engineering, electrical & electronic