A Voltage Correction based Inverse-time Overcurrent Protection Scheme Considering Distributed Generation Stable Infeed Effect

YU Kun,LIN Xiangning,LI Hao,ZHAO Hang,LI Zhengtian,HUANG Jingguang,BO Zhiqian
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.162218
2018-01-01
Abstract:To solve the problem that traditional protection scheme can hardly satisfy the requirements of both coordination and sensitivity with distributed generation (DG) infeed effect, the operating behavior characteristics of inverse-time overcurrent protection with the changing of fault location with and without DG connection were revealed. The impacts of DG to the performance of inverse-time overcurrent protection were analyzed. A voltage correction based inverse-time overcurrent (VCITO) protection method with high sensitivity was proposed in this paper. Voltage correction factor and voltage correction gradient exponent, which are constructed based on the voltage natural distribution under fault and the change law of measuring voltage with the changing of fault location, was used to correct the inverse-time characteristic curve. The operating time of VCITO protection was obtained based on local information and it can ensure the coordination meanwhile the optimization of operating speed. A typical 35kV model with DG was established in PSCAD/ EMTDC and the simulation results proved that VCITO protection can solve the coordination and operating speed problems with DG connection and its sensitivity is high.