Performances of Gas Turbine-Based CCHP System Combined With Solar and Compressed Air Energy Storage

YANG Cheng,WANG Xusheng,ZHANG Chi,MA Xiaoqian
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.161374
2017-01-01
Abstract:In gas turbine based combined cooling,heating and power (CCHP) system,the operation mode of following thermal load often causes electric power surplus and efficiency decrease at part load.In this paper,we proposed a gas turbine based CCHP system combined with solar and compressed air energy storage (S-CAES).To obtain the off-design characteristics of this system and each subsystem,the typical off-design model of CCHP and Aspen Plus models of S-CAES were built.This paper also analyzed the operation characteristics of this system in different energy storage rates,and compared the effects of two different operation modes between adjust air reservoir discharge flow and adjust air turbine inlet temperature on the system.Finally,this kind of system was applied to a hotel building of South China as a case study.Results show that compared with gas turbine based CCHP system without energy storage,the energy consumption can be reduced by 16.57,15.94,11.87GJ and the primary energy ratio will increase by 5.68,7.88 and 4.69 percentage points for the typical day of summer,transition season and winter,respectively.
What problem does this paper attempt to address?