Stage Identification in Air-gap Discharge of Oil-impregnated Paper Insulation Based on Wavelet Packet Energy Entropy

CHEN Weigen,XIE Bo,LONG Zhenze,CUI Lu,LI Yongsen,ZHOU Qu,CHEN Xi
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2016.02.030
2016-01-01
Abstract:Air-gap discharge is the main type of partial discharge (PD) within power transformer. It is of great significance to study the discharge development stage for the monitoring and diagnosis of transformer potential faults. This paper build an air-gap discharge model in simulative transformer tank, collecting PD signals based on constant voltage method, utilizing wavelet packet decomposition method to partition the PD signal bands obtaining signal energy distribution in each frequency band as well as total signal energy tendency along with PD development process. The new PD parameter describing the development process, wavelet packet energy entropy, was proposed based on the signal energy variation in each frequency band. Due to the cyclic change of wavelet packet energy entropy, the step points of wavelet packet entropy are taken as the way to effectively divide the PD development stage. According to the thresholds of wavelet packet energy entropy in different stages, the PD development stages were identified.
What problem does this paper attempt to address?