Combined Emergency Control Strategy of Generator Tripping and Load Shedding Based on the Characteristics of State Plane

WANG Huaiyuan,ZHANG Baohui,YANG Songhao,SU Fu
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.151638
2016-01-01
Abstract:A combined emergency control strategy of generator tripping and load shedding was proposed. When power system subjected to disturbances loses synchronization, the strategy can prevent system instability and also improve the frequency and voltage. By analyzing the characteristic of the phase-plane trajectory representation of power angle and rotor speed, the relationship between the unbalanced power and the slope of the trajectory is obtained. Based on the kinematic equation of the rotor, the expression of the relationship between the unbalanced power and the slope is deduced and the control algorithm is derived. And then, the start-up condition of the combined control strategy is presented and the allocation algorithm of generator tripping and load shedding is given. The simulation results in IEEE 39-bus system and the Sanhua system validate the effectiveness of the combined control strategy.
What problem does this paper attempt to address?