Configuration Scheme of STATCOM for Mitigating Simultaneous Commutation Failure Risk of Multi-Infeed HVDC Links

ZHENG Kuan,SHEN Chen,LIU Feng
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.2521
2018-01-01
Abstract:In recent years,multi-infeed HVDC links have emerged in regional power grids.As several DC links may be terminated in close vicinity,a severe short-circuit fault occurring in receiving grid may cause simultaneous commutation failures (SCFs) of the multi-infeed HVDC links,even their forced blocking.That could lead to serious consequences.Recognizing voltage sags and/or distortion are the main factors triggering SCFs,retaining amplitude of commutation voltage during the fault by installing STATCOM turns to be a potential countermeasure to mitigate SCF risk.This paper firstly defines expected number of SCFs caused by a given set of short-circuit faults as SCF risk measure.It can be calculated by considering a number of fault positions spreading over the AC system and an expected number of occurrences per year (failure rate) assigned to each fault position.Then this paper screens out those medium-faults to consider for reducing computational burden.Optimal sizing of STATCOMs is formulated as a stochastic optimization problem considering SCF risk.Considering difficulty in solving this problem due to its high dimension and non-convexity,genetic algorithm is adopted.Numerical experiments carried out on an AC/DC system modified from standard IEEE 1 18-bus system empirically certify effectiveness of the proposed method.