An Analytical Solution for Transient Process of HVDC Transmission System Part 2 - Algorithm and Example

LI Chongtao,LIN Xiao,ZHAO Yong,ZHAO Ligang,DU Zhengchun,XIA Daozhi
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.0580
2017-01-01
Abstract:An accurate calculation method for transient process of HVDC transmission system was proposed in this paper. Calculation for main HVDC equipment and control system were conducted separately. Main equipment was described in piecewise homogeneous linear differential equations with solutions obtained with analytical method. Control system containing non-linear courses was calculated with a step-changed integration method. Accurate time-domain response was obtained by combining the two methods. By using analytic solution instead of numerical integration method for transient process in main HVDC equipment, calculation process is no longer be limited by small step length, and has no truncation errors and numerical stability problem. A typical example was presented and analytical solution results were compared with PSCAD/EMTDC simulation results to verify validity andefficiency of the proposed method.
What problem does this paper attempt to address?