Adaptive Quasi-PRD Control Method of Grid-Connected PV Inverter in Weak Grid

LIU Guihua,SHI Tong,MA Tianyuan,WANG Wei
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.0289
2017-01-01
Abstract:When grid-connected photovoltaic (PV) inverter is connected to weak grid, high equivalent impedance of weak grid can lead to small bandwidth of control system and poor control performance. Aiming at this problem, this paper proposes an adaptive quasi proportion resonant differential (quasi-PRD) control method. This method firstly uses quasi-PRD controller to replace traditional PI controller to realize zero steady-state error tracking and expand system bandwidth. Then, double harmonic current injection method is applied to implement on-line detection of grid impedance. Finally, the detected impedance value is used to on-line adjust controller parameters of quasi-PRD. Simulations and experiments were performed, verifying that the proposed method can not only increase bandwidth and dynamic response speed of control system, but also improve system adaptability for different grid impedance values, and eventually improve power quality.
What problem does this paper attempt to address?