Evaluation of economic operation for microgrid with complementary DGs and energy storage

Yonghong XIA,Hongjian WU,Jianbo XIN,Lin CHENG,Yunjun YU,Xiaofeng WAN
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.07.010
2017-01-01
Abstract:Since the wind and solar energy sources have high short-term fluctuation while the hydraulic energy source has small short-term fluctuation,the complementary relationships among them are analyzed,an optimal configuration method is proposed for the microgrid with complementary DGs(Distributed Generations) and energy storage,and an evaluation system is built to assess the influence of its complementary performance on the economic operation of microgrid.The proposed method sets the capacity of energy storage system,the installation cost of microgrid devices and the cost of system operation and maintenance as the objectives,takes the system capacity,the proportion of DG and the charge/discharge characteristics of battery as the constraints,and applies the adaptive genetic algorithm to obtain the optimal capacities of DGs and the related capacity of energy storage system.The capacity of energy storage system and the evaluation index of economic operation for a certain configuration can be obtained by flexibly adjusting the combination mode and proportion of DGs.Results show that:when the power outputs of DGs,such as wind,solar and hydraulic are complementary,the capacity of energy storage system is significantly reduced and the economic benefit of microgrid is optimal.
What problem does this paper attempt to address?