Power system equivalence for practical engineering

Lin ZHU,Jun GE,Xueguang WU,Dong LIU,Song ZHANG,Lu GAO
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.09.025
2017-01-01
Abstract:AC system equivalence is needed in HIL(Hardware-In-Loop) test to give the considerations of simulation scale and interaction between AC and DC,for which,a method of large-scale AC system equivalence is proposed based on the principle that the short circuit capacities before and after equivalence should be consistent.The rated capacity and access reactance of equivalent generator are set according to the short circuit current of equivalent node.A new criterion is proposed based on the short circuit current contribution ratio according to the relationship between short circuit current and dynamic system characteristics,which is used to choose the dominative controller of equivalent generator and calculate the controller parameters.The static Ward equivalence is improved to eliminate the conditions of negative resistance and negative generator active power output.As an example,the system voltages,power flows and short circuit capacities before and after equivalence are compared and the post-fault dynamic response characteristics are analyzed,verifying the effectiveness of the proposed method.
What problem does this paper attempt to address?