Characteristic admittance model and PD amplitude distribution of tunnel-installed high-voltage cables

Xiaoxin CHEN,Yong QIAN,Yongpeng XU,Gehao SHENG,Xiuchen JIANG
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.07.026
2017-01-01
Abstract:In order to study the amplitude distribution of PD(Partial Discharge) signals in cross-bonded cables,a parameterized characteristic admittance model of three-phase tunnel-installed cable is established based on Tylavsky's formulas to calculate the amplitude distribution of PD pulse current on the cross-bonded cables.The influences of cable laying mode and tunnel environment on the amplitude distribution are studied.The accuracy of the proposed model and the correctness of the obtained conclusions are verified by simulation experiments and field tests.Research shows that,with the characteristic expression of "two-larger-one-smaller",the amplitude distribution of PD signals is decided by the characteristic admittance ratio;the amplitude difference among three phases is reduced along with the increase of the space between cable centres and the distance between the cable centre and the inner wall of tunnel.