Output impedance modeling of virtual synchronous generator and its adaptability study in a weak grid

Gang HAN,Xu CAI
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.12.016
2018-01-01
Abstract:The interaction stability of the virtual synchronous generator integrated power network in weak grid conditions is studied.Based on the influence of main circuit parameters and control parameters,the output impedance model of virtual synchronous generator in dq rotating coordinate system is established and its analytical expression is derived.The frequency characteristic of the output impedance is analyzed,obtaining the conclusion that the virtual synchronous generator is easy to be unstable in a weak grid.Based on the generalized Nyquist criterion,the influences of grid strengths and power loop control parameters on the stability of virtual synchronous generator are studied,based on which a method of stabilization control for virtual synchronous generators based on increasing active loop parameters is proposed to improve the adaptability of virtual synchronous generators in a weak grid.Simulation in the RTDS-based hardware-inloop simulation platform verifies the correctness of the theoretical analysis.
What problem does this paper attempt to address?