DVR with double-stage LC filter

Jintao YANG,Jian LE,Kaipei LIU,Yingduo HAN
DOI: https://doi.org/10.16081/j.issn.1006-6047.2016.08.011
2016-01-01
Abstract:The DVR(Dynamic Voltage Restorer) with double-stage LC filter is applied to eliminate the influence of load harmonic current on the output voltage of DVR with single-stage LC filter and to filter out the switching-frequency harmonic with smaller inductance and capacitance.The mathematical model of DVR with double-stage LC filter is established and its system stability is analyzed according to Routh criterion.The parameter design of its control system is proposed and its response performance is compared with that of DVR with single-stage LC filter.Simulative and experimental results prove that,the DVR with doublestage LC filter suppresses the influence of load harmonic current on the DVR system to effectively enhance its output voltage quality.
What problem does this paper attempt to address?