State Estimation Method for SoIving Reactive Power ProbIem in Looped Networks

Yi Sun,Guangyu He,Shuai Fan,Shaopeng Zhai
DOI: https://doi.org/10.3969/j.issn.1000-3886.2019.03.033
2019-01-01
Abstract:Due to large amounts of circular structures existing in the power transmission network, low accuracy of reactive measurement and its frequent bad measured data, the weighted least squares state estimation method is so vulnerable to residual pollution that it can hardly pass the examination on state estimation qualification rate. Based on the conception of normal measuring point, a measuring point evaluation function was established in this paper, considering the uncertainty of the measuring equipment, in order to judge whether a measuring point is normal or not. Furthermore, a new state estimation model was set up under consideration of actual system constraint and power flow constraint, taking the minimal number of abnormal points as the optimization objective. Compared with bad data identification method used for residual analysis, the proposed approach had significant advantages in the respect of solution efficiency and accuracy. Analysis of an actual transmission network model as well as its telemetering and telesignalization data in a certain city indicated that the indexes for the qualification rate of state estimation measuring point were improved and the validity of the proposed approach was verified.
What problem does this paper attempt to address?