Automatic discovery of power system electrical zones considering stations in split operation mode as well as stations without initial geography zone

Feng ZHAO,Hong-bin SUN,Zhi-wen YU,Qing-lai GUO,Wen-xin GUO
2014-01-01
Abstract:As substations in split operation mode as well as stations without initial geography zone can’t be considered and treated in the previous automatic discovery method of power system electrical zones based on electrical distance, an automatic discovery method of power system electrical zones considering stations in split operation mode as well as stations without initial geography zone is proposed. Through dividing the substation in split operation mode into several new stations and rebuilding the topological connections between the several new substations and other stations in power system, the real-time operation status of power grid can be reflected more accurately. According to the average electrical distance and power transmission between stations without initial geography zone and geography zones in power system, stations without initial geography zone are put into the initial geography zones with closest connections, which makes the automatic discovery of power system electrical zones more reliable. A test case is done in Guangdong Power Grid of China. The results show that the proposed method considers the real split operation status of substations accurately, covers all of the stations, and the results of electrical zones agree with that of the experience of operators, so the results are reliable.