Modified Modeling And System Stabilization Of Shunt Active Power Filter Compensating Loads With F Capacitance

Yiqiao Liang
DOI: https://doi.org/10.3390/en12112084
IF: 3.2
2019-01-01
Energies
Abstract:The interactions between shunt active power filter (APF) and capacitance load tend to result in stability problems and resonance. The conventional model of a shunt APF is not precise enough to reflect this phenomenon. To address it, this paper proposes a modified shunt APF system model to accurately reflect various stability problems. This paper also studies the mechanism of positive feedback resonance brought by capacitance load and proposes a modified hybrid controller to improve the stable margin of the system, making the shunt APF work stably under different working conditions where there are F capacitors on the demand side. The correctness and validity of the proposed strategy are verified by simulation analysis and prototype experiments.
What problem does this paper attempt to address?