Using Radiant Cooling Desk for Maintaining Comfort in Hot Environment

Yingdong He,Nianping Li,Meiling He,De He
DOI: https://doi.org/10.1016/j.enbuild.2017.04.013
IF: 7.201
2017-01-01
Energy and Buildings
Abstract:This study aims to investigate thermal comfort of subjects with a new type of radiant cooling desk in hot environment. A series of experiments was conducted in an experimental room at 28, 30 and 32 degrees C in summer. Totally, 20 subjects (10 males and 10 females) participated in the experiments. During the test, subjective responses and some parameters of radiant cooling desk were recorded. The obtained results indicate that radiant cooling desk reduced warm sensation and increased both comfort and acceptability of subjects in hot environment, while it weakened the preference for cooler environment. Radiant cooling desk mainly cooled upper body parts and this effect was more significant in warmer environment. Besides, subjects were free from draft risk but they still wanted higher velocity in hot environment. In addition, the surface temperature of radiant panels at 28, 30 and 32 degrees C were 22.8, 23.9 and 25.5 degrees C respectively, which lowered condensation risk. And the cooling capacity of radiant cooling desk at 28, 30 and 32 degrees C were 89.9, 104.4 and 130.7 W, respectively. Since radiant cooling desk can extend acceptable temperature range and use high-temperature supply water, it has large potential for energy conservation. (C) 2017 Elsevier B.V. All rights reserved.