Research on a Novel Lossless Soft-switching Topology Based on Buck-Boost Converter in UPS System

LIANG Liang,HE Jun-ping,GUO Kun,CAI Xiong-bing
DOI: https://doi.org/10.3969/j.issn.1000-100x.2011.01.028
2011-01-01
Abstract:In order to decrease great consumption during switching process caused by the hard-switching in a uninter-ruptible power supply(UPS) discharge system,a novel passive lossless soft-switching(PPSS) topology based on Buck-Boost converter is proposed.Consumed energy on IGBT is transferred and fed back to load by using snubber circuit with inductance,capacitance and diode.Firstly,the controlling thoughts and different operation modes are introduced.Secondly,stress of the switch elements is analyzed and the parameter condition that must be satified by the capaci-tance and inductance is discussed.A 4 kW UPS discharge system converter prototype is built up,and it can operate in the ZCS and ZVS condition,obtains higher working efficiency than traditional hard-switching modes.The experimen-tal results verify the validity of this topology.
What problem does this paper attempt to address?