Asymmetrical Model of Six-Phase Delta-Connected Autotransformer

GAO Lei,TONG Weiming,MENG Fangang
DOI: https://doi.org/10.3969/j.issn.1006-6047.2011.12.001
2011-01-01
Abstract:A completely decoupled model of delta-connected autotransformer is built to analyze the effect of the asymmetry of phase shift transformer on the 12-pulse rectifier.By analyzing the coupling circuit of autotransformer,the relationships among branch voltage,branch current,node voltage and node current are obtained and a node admittance matrix is derived for describing the information of winding connection pattern,electrical parameters and so on.Based on the matrix,a completely decoupled model of delta-connected autotransformer is built and the relationship between model parameters and practical parameters is obtained.Simulative and experimental results verify the effectiveness of the model in simulating the asymmetry of delta-connected autotransformer.
What problem does this paper attempt to address?