Simulation and Discussion on Mechanism of Dynamic Interaction Between Frequency and Voltage in Islanded Power Grid

YANG Hao,ZHANG Baohui,SONG Yunting,CHEN Dezhi,WANG Huaiyuan,YANG Songhao
2013-01-01
Abstract:At present the under-frequency load shedding device and the under-voltage load shedding device are configured in power grid independently. When these devices are applied in the secure control of frequency and voltage in an islanded power grid, due to the intercoupling of dynamic processes of voltage and frequency it is impossible to accurately judge the frequency variation of the islanded grid only by initial active power vacancy. Through the simulation of typical example, the impacts of initial active power vacancy, initial reactive power vacancy, load characteristics, etc. on dynamic process of island frequency are analyzed, and it is pointed out that the load characteristics and initial reactive power vacancy intensively impact on both island voltage condition and dynamic variation of island frequency. During the research on post-splitting dynamic frequency in the island with a lot of active power vacancy it is necessary to fully consider the impact of voltage variation on dynamic frequency. Conclusion of this research is available for reference to joint emergency control of island frequency and voltage after the splitting of power grid.
What problem does this paper attempt to address?