Structural Optimization of FR-Type Dampers for 330 Kv Transmission Lines

莫娟,黄廷政,刘胜春,彭宗仁,谢梁
DOI: https://doi.org/10.13335/j.1000-3673.pst.2011.12.027
2011-01-01
Abstract:The FR-3 type damper used in 330 kV transmission lines is of complex structure, e.g., the damper head is similar to the form of tuning fork and the radius of curvature at both its ends is too small, and these structural features lead to higher electric field strength, so corona discharge during actual operation may occur due to such a structure and electromagnetic pollution of ambient environment may take place. A three-dimensional model of FR-3 type damper is built by finite element method (FEM) to perform simulation of electric field, and the distribution regularity of electric field of the damper is achieved and on this basis the structure of tuning fork of the damper head is optimized, thus the maximum electric field strength is from 3 000 kV/m reduced to 2 170 kV/m. Manufacturing prototypes according to the optimized structure of the damper, the corona tests and power characteristic tests are performed under different altitudes, and testing results show that adopting the optimized damper the corona discharge can be effectively prevented at the altitude lower than 3 500 meters, meanwhile its resonant frequency and power consumption can meet the requirement. The peak resonant power to valley resonant power ratio of the optimized structure under different resonant frequencies is better than that of the not optimized structure, therefore the optimized structure of the damper possesses better vibration-preventing performance.