Study of Load Frequency Control for Three-Area Time-Delayed Power System

XIONG Linyun,WANG Jie
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.1585
2018-01-01
Abstract:Employment of communication channels inevitably results in advent of time delays in load frequency control (LFC) schemes. Existence of such time delays exerts potential threats on stability of power systems. This paper studies a three-area time-delayed power system and proposes a linear matrix inequality (LMI) based robust LFC scheme with delay margin estimation (DME). A recursive substitution procedure is proposed to eliminate transcendental terms of characteristic equation and root tendency is introduced to analysis stability of frequency domain roots. Analytic form of delay margin is subsequently provided. Then LMI based robust controller design procedure is proposed based on DME, wherein robust performance index (RPI) is introduced to evaluate impact of external disturbance on system outputs. The robust controller gains are ultimately obtained with the estimated delay margin and binary search technique (BST) aiming to find the minimum RPI value. A two-step simulation is conducted to evaluate performance of the proposed scheme. The first step is conducted to verify effectiveness of DME, and the second step aims to assess performance of the proposed scheme with conventional methods. The simulation results indicate that the DME procedure is effective and the proposed control scheme has superior performance over conventional LMI based robust control schemes.