An Accurate Power Control Scheme for Droop-Controlled Grid-Connected Inverters

Baojin Liu,Jinjun Liu,Zeng Liu,Teng Wu,Ronghui An
DOI: https://doi.org/10.1109/apec.2018.8341348
2018-01-01
Abstract:Grid-connected inverters based on droop control have been widely used in distributed generation (DG) systems, as they can ensure smooth transition between grid-connected mode and islanded mode. The traditional active power-frequency (P-f) droop and integrator aided reactive power-amplitude (Q-V) droop control method can track the power command precisely if the grid is stiff enough. However, if the grid frequency fluctuates from its rated value, the active power will sustain steady state tracking error. To solve this issue, this paper proposes an accurate power control scheme, in which an integrator is added to the active power control loop, similar to that in reactive power loop. By doing so, this control scheme can ensure excellent power tracking performance even with grid frequency and amplitude disturbances. Simulation and experimental results are provided to validate the proposed control scheme.
What problem does this paper attempt to address?