Research On Dc Infeed Ratio Of Receiving Grids With Renewable Energy Under Frequency Stability Constraint

Dajun Si,Yingchun Qian,Facai Xing,Huanfeng Dong,Mingyuan Guan,Zheng Xu
DOI: https://doi.org/10.1049/joe.2017.0698
2017-01-01
Abstract:With the rising renewable energy penetration and large capacity power infeed, receiving grids are challenged by the decreasing rotational inertia as well as primary frequency regulation ability and the increasing single dc infeed power. Based on the steady-state and transient-state frequency stability constraints, this paper proposes a method to calculate the critical single dc infeed ratio with different renewable energy penetration and dc infeed ratio. Taking into consideration the renewable energy penetration and dc infeed ratio, the paper first modified the traditional frequency deviation index. Then, the electromagnetic transient model of the receiving grid with renewable energy is established in PSCAD/EMTDC, and the influence of the gain coefficient in emulation inertia controllers, the installed capacity of wind farms and the hydro power ratio on critical single dc infeed ratio were studied. The critical single dc infeed ratio is one of the operating requirements of the receiving grid, and it provides reference for installed capacity in power system planning.
What problem does this paper attempt to address?