Exergy Analysis Of A Heat Exchange Substation Based On Cascading Heat Supply

Peng Wang,Shuran Ji,Weixin Zhao,Hua Zhao
DOI: https://doi.org/10.1016/j.proeng.2017.10.198
2017-01-01
Abstract:When radiator and floor radiant heating users coexist in the same heat exchange substation, simply parallel connection of the user systems or the heat exchangers cause high return water temperature. Since the return water temperature of radiator heating system is generally about equal to the supply water temperature of floor radiant heating system, a cascading heat supply connection is proposed to apply in heat exchange substation. The cascading heat supply connection considers eleven conditions to meet the combination of flow rate and water temperature from each user. Using exergy analysis method, each condition is analyzed. The results of case study show that the return water temperature of secondary network in the cascading connection can be reduced by 2-11.; the flow rate of secondary network decreases by 7%-30%; and the exergy utilization rate is higher than traditional connection. According to the analysis of influencing factors, reference temperature and primary supply temperature correlate negatively with exergy utilization rate, while flow rate ratio and secondary supply temperature have positive correlation. During heating period, the cascading heat supply connection performs better exergy utilization as the rise of outdoor temperature. (c) 2017 The Authors. Published by Elsevier Ltd.