Abstract:A liquid cooling system with a pump serving as a cold plate was proposed. For direct contact with the heat source, the structure of the pump (centrifugal pump) used in conventional liquid cooling system was modified. Experiments under different heat flux density were performed to evaluate the thermal performance of the proposed system. To further understand the internal flow and heat transfer of the proposed system, numerical simulations were conducted. The accuracy of the numerical model was proven by comparison with experimental results, the error reached maximum 7.78% at heat flux q = 83.8 W / cm2. Both the experiments and numerical results showed that the proposed system shows good heat dissipation ability, the maximum convective heat transfer coefficient is calculated as 18.9 kW / m2 k. Moreover, the structure of the system is more compact and practical.