Nh3-H2o Water Source Absorption Heat Pump (wsahp) for Low Temperature Heating: Experimental Investigation on the Off-Design Performance

Wei Wu,Siyuan Ran,Wenxing Shi,Baolong Wang,Xianting Li
DOI: https://doi.org/10.1016/j.energy.2016.09.058
IF: 9
2016-01-01
Energy
Abstract:Heat supply systems based on absorption heat pump were assessed to have great potentials on energy savings and emissions reduction. A prototype of NH3-H2O water source absorption heat pump (WSAHP) designed for low temperature heating was experimentally investigated under different working conditions. The effects of driving source, hot water and source fluid temperature on the heating performance were studied. As driving source increases from 110 degrees C to 140 degrees C with 15 degrees C evaporator inlet and 45 degrees C hot water, COP increases from 1.429 to 1.552 and then decreases to 1.495, while the heating capacity increases from 32.23 kW to 88.35 kW. As hot water increases from 30 degrees C to 45 degrees C with 130 degrees C generator inlet and 15 degrees C evaporator inlet, COP decreases from 1.653 to 1.449, while the heating capacity drops from 94.55 kW to 60.37 kW. As the source fluid increases from 10 degrees C to 30 degrees C with 130 degrees C generator inlet and 45 degrees C hot water, COP increases from 1.203 to 1.609, while the heating capacity increases from 39.51 kW to 79.72 kW. Comparisons with former work indicate that the developed prototype can operate under evaporator inlet temperatures as low as -18 degrees C, which is significant to improve heating applicability in colder conditions. (C) 2016 Elsevier Ltd. All rights reserved.