Electric Field Calculation and Grading Ring Design for 330kv Terminal Tower with Composite Cross-Arms

Jialong Wang,Zongren Peng,Hao Wu,Hongwei Deng,Hao Liu,Chuang Wang
DOI: https://doi.org/10.1109/icd.2016.7547615
2016-01-01
Abstract:In order to analyze the potential and electric field distribution of one 330kV AC terminal tower with composite cross-arms, the full three-dimensional (3D) finite-element method (FEM) model was established for numerical simulation, using software ANSYS. The influences of tower, earth, wires and interphase interaction were considered. The distributions of potential and electric field on the cross-arms, insulators and fittings were calculated with FEM harmonic analysis. Based on the calculation results in the original design, a grading ring configuration scheme of the composite cross-arms and insulators was proposed. And the structure parameters of grading rings were optimized. The calculation results show that in the original design, the maximum E-field strength on the silicone rubber (SIR) housings is 1156V/mm, and that on the rings is 3112V/mm. While in the optimized design, the maximum E-field strengths on the SIR housings and rings are 389V/mm and 2279V/mm respectively. It could be inferred that after optimization, the voltage-sharing performance of composite cross-arms and insulators has been improved, and the E-field strength of each key location on the terminal tower was proved to be lower than the critical value.