Distance Protection Optimization Strategy for Distribution Systems with Battery Energy Storage System

Lian Yang,Nengling Tai,Chunju Fan,Wentao Huang
DOI: https://doi.org/10.1063/1.4950941
IF: 2.847
2016-01-01
Journal of Renewable and Sustainable Energy
Abstract:Battery Energy Storage System (BESS) is a type of clean energy, which is able to enhance energy efficiency. However, the connection of the BESS with distribution systems has an impact on the conventional protection. This paper presents the BESS operation characteristics and its impact on distance protection. Optimal strategy of Zone II is analyzed from the perspective of impedance originally. The BESS has three operation statuses which will be studied separately. When a fault occurs at different locations of feeders downstream, the fault current of the BESS increases nonlinearly. By defining two original concepts, critical impedance and maximum protection impedance, the nonlinear output current is classified into two parts. Protect access capacity and protection sensitivity are analyzed under both situations. Modifying value m is presented to solve this protection-related problem. Minimum and maximum values of m are calculated to avoid overreach or blinding operation. After optimized by m, Zone II protection can trip correctly. Analysis and simulation results, based on two practical distribution systems, verified the effectiveness of the optimization strategy.
What problem does this paper attempt to address?