Transient Stability Analysis of South China Power System with Multiple HVDC Links

徐政,杨靖萍,高慧敏
DOI: https://doi.org/10.3969/j.issn.1003-6520.2004.11.009
2004-01-01
Abstract:In this paper, the transient stability of South China power system with three HVDC links is analyzed. The fault modes include N-1 contingencies, single pole block of each HVDC link, double pole block of each HVDC link, and simultaneous double pole block of multiple HVDC links. The generator tripping and load shedding schemes are also studied. The results show that the system is stable if any single circuit of Guangdong 500 kV grid is three phase short circuited and then tripped. For double pole block fault in Tian-Guang or San-Guang HVDC link, the system is stable, but Gui-Guang HVDC link double pole block requires multiple generator tripping in the power sending end of Guizhou to keep the system stable.