Active disturbance rejection control in thermal power unit coordinated control system

Jia Luo,Qianru Xu,Donghai Li,Shihe Chen,Yaqing Zhu,Wenjun Wan
DOI: https://doi.org/10.11719/com.app.chem20141105
2014-01-01
Abstract:A Considering the situation that normal coordinated control strategy can not meet the requirements of network automation load control when large coal-fired thermal power plants run with unmeasured pulverized coal disturbance,frequently uncertainty external disturbances and complex control object,a boiler-turbine coordinated control strategy combing feedforward compensation and approximate static one-way decoupling control structure with Active Disturbance Rejection Control(ADRC) was proposed.Thermal power unit with strong coupling and external disturbance in Turbine-Boiler control loops could fast and stably trace power grid load command by ADRC tracking and compensating the disturbance.Meanwhile,this strategy has strong robustness on operating conditions changing of the unit and the model uncertainty.The simulation results showed that the designed control method not only adapt to power and coal feeder rotate speed of coordinated control system disturbance and model parameters perturbation but also has good dynamic characteristics.
What problem does this paper attempt to address?