Influence of Freezing Conditions on the Safety of Grounding Systems

HE Jinliang,SUN Weimin,ZENG Rong,GAO Yanqing,PAN Xiyuan,HU Jun
DOI: https://doi.org/10.3321/j.issn:1000-0054.2000.03.004
2000-01-01
Abstract:High resistivity soil layer forms when the ground freezes during the winter. The influence of the high resistivity layer on the safety of grounding system was analyzed numerically. The grounding resistance and the step and touch voltages of the grounding system increase with the thickness or resistivity of the high resistivity soil layer. If the thickness of the high resistivity soil layer is smaller than the burial depth of the grounding grid, the safety of the grounding system is not affected; but when the thickness exceeds the burial depth of the grounding grid, the grounding resistance and the step and touch voltages increase greatly and the safety of the grounding system is greatly reduced. So the thickness of the high resistivity soil layer at a substation should be accurately estimated and the grounding grid should be buried below the high resistivity soil layer so the safety of the grounding system would be assured throughout the year. The results provide a design basis for power systems.
What problem does this paper attempt to address?