Resilience-oriented Comparative Study of SOP-based Service Restoration in Distribution Systems
Wei Zhang,Cong Zhang,Jiayong Li,Shiran Cao,Dapeng Wang,Huaizhi Yang,Jieming Du,Zhikang Shuai
DOI: https://doi.org/10.1016/j.epsr.2023.110050
IF: 3.818
2024-01-01
Electric Power Systems Research
Abstract:Soft open points (SOPs) can perform load shifting and voltage improvement, and are critical to improving distribution service restoration (DSR) during power outages. Although multiple DSR strategies utilizing local resources have been reported, their effectiveness has not been sufficiently studied. To solve this problem and utilize the flexibility of SOP, a comparative study of different strategies for SOP-based DSR is presented in this paper. First, various SOP-based DSR models, including single-source, single-island model (SSM), islanding partition model (IPM) and multi-source collaborative model (MCM), are proposed and formulated as mixed-integer nonlinear programming (MINLP) problems, incorporating static voltage characteristics of loads. Second, to enhance the solution efficiency, mixed-integer second order cone programming is introduced to convert the MINLP problems into easily solvable convex optimization problems. A restorative index is defined to evaluate the effectiveness of various SOP-based DSR strategies. Finally, a comparative simulation analysis of the proposed models on the IEEE 33-bus system illustrates that SOP-based MCM achieves an 94 % power output for distributed energy resources, while exhibiting the lowest RI for the total loads, standing at just 9.5 %. Furthermore, the RI for critical loads consistently remains at 0, demonstrating the superiority of SOP-based MCM in comparison to other strategies.