Auxiliary Control Strategy of DFIG’s GSC During Network Unbalance Based on Reduced-Order Resonant Controller

Wang Jianliang,Zhang Yihuang,Cheng Peng,Nian Heng
DOI: https://doi.org/10.3969/j.issn.1000-6753.2015.04.005
2015-01-01
Abstract:In order to develop the operation performance of the overall DFIG generation system under unbalanced grid voltage conditions, the auxiliary control of the gird-side converter(GSC) must be taken into account. A current control scheme, using a reduced-order resonant controller(RORC), is proposed in this paper so as to achieve the selectable control targets, i. e., removing the oscillations in the active or reactive power. In this control strategy, the active(or reactive) power oscillations are directly to be controlled by RORCs in the synchronous reference frame. As a result, the reference calculations of the negative sequence currents and the sequential separations of the measured voltage are avoided. Simulation and experimental results are provided to demonstrate the availability of the proposed control strategy using RORCs.