Analysis of the interface pressure of cold shrinkable joint of 10 kV XLPE cable

Jia Zhidong,Zhang Yujin,Fan Weinan,Zhu Bin,You Jiao,Lu Guojun
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170123041
2017-01-01
Abstract:In recent years, cold shrinkable joints are widely used in 10 kV XLPE cable line. Interface pressure is an essential parameter which determines the performance of cold shrinkable joints. However, relevant contents of interface pressure are barely seen in both international and national standards, which makes it harder for quality control and performance test of cold shrinkable joints. For this reason, the theoretical calculation model of the cable joint is proposed and the calculation formula of the interface pressure is deduced. The test of measuring the interface pressure is applied using cold shrinkable tubes in different sizes from different manufacturers as samples and embedded sensors as test method. The test results indicate that the interface pressure will ascend to stable value after installation of the joint. Minor relative errors between test results and theoretical calculation verify the validity of the theoretical model and interface pressure calculation formula. In this way, the research results can provide references to future quality test before new cable joints are put into operation and therefore improve the reliability of cable lines in distribution network. © 2017, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
What problem does this paper attempt to address?