Experimental Study of the Effect of Inclination Angle on the Thermal Performance of Heat Pipe Photovoltaic/thermal (PV/T) Systems with Wickless Heat Pipe and Wire-Meshed Heat Pipe

Mingke Hu,Renchun Zheng,Gang Pei,Yunyun Wang,Jing Li,Jie Ji
DOI: https://doi.org/10.1016/j.applthermaleng.2016.06.003
IF: 6.4
2016-01-01
Applied Thermal Engineering
Abstract:Two different heat pipe photovoltaic/thermal (PV/T) systems, namely, wickless heat pipe PV/T system and wire-meshed heat pipe PV/T system, were proposed. In this paper, the thermal performances of the two systems working on different inclination angles were experimentally investigated in an Enthalpy Difference Laboratory with a solar simulator. The thermal performance of the wire-meshed heat pipe is not as sensitive to the inclination angle as that of the wickless heat pipe. The wickless heat pipe PV/T system is recommended at latitudes higher than 20 degrees, whereas wire-meshed heat pipe PV/T system is suggested at latitudes lower than 20 degrees. Moreover, the thermal performances of both PV/T collectors at an inclination angle of 40 degrees were further investigated, in which case both heat pipes worked at optimum conditions. The thermal efficiency of the wickless heat pipe PV/T system and wire-meshed heat pipe PV/T system at zero reduced temperature was 52.8% and 51.5%, respectively. (C) 2016 Elsevier Ltd. All rights reserved.