Design of serial alarm systems based on deadbands and delay timers for removing false alarms

Poku Gyasi,Jiandong Wang
DOI: https://doi.org/10.1016/j.psep.2022.05.006
IF: 7.8
2022-06-01
Process Safety and Environmental Protection
Abstract:Alarm deadbands and delay timers are widely used in practice to remove false alarms. This paper proposes a method to design serial alarm systems that are composed of alarm deadbands serially followed by delay timers. Serial alarm systems are effective for removing false alarms with different types of alarm deviations and alarm durations, while alarm deadbands or delay timers alone are suitable only for one type of false alarms. A minimization problem is formulated to simultaneously design optimal values of the alarm deadband width and delay timer factor, for achieving a desired ratio of false alarms to be remove. Bayesian estimation approach is exploited to resolve a main technical challenge in achieving reliable estimates of joint probabilities of alarm deviations and alarm durations. Existing methods are confined to the isolated design of alarm deadbands or delay timers based on probability density functions of process variables, and are subject to a restrictive assumption that process variables are independent and identically distributed. By contrast, the proposed method is for the joint design of serially-connected alarm deadbands and delay timers; it is based on joint probabilities of alarm deviations and alarm durations, and does not require the restrictive assumption. Numerical and industrial examples are provided to illustrate the proposed method and compare with existing ones.
engineering, environmental, chemical
What problem does this paper attempt to address?