Abstract:Control strategy under unbalanced grid voltage conditions is one of the most important issues for grid-connected inverter. Under unbalanced grid voltage conditions, the 2nd active and reactive power ripples generate, they pollute the grid. To meet the demands of IEEE Std.929-2000, this paper proposed a modified power compensation control strategy; the proposed solution is based on direct power control. To provide accurate compensating power, the power model of three-phase inverter under unbalanced grid voltage conditions is given, using the positive sequence current component and the negative sequence voltage component, the compensating powers are calculated in details. Theoretical analysis and comparative simulation verification are presented to demonstrate the effectiveness of the proposed control strategy.
What problem does this paper attempt to address?