A Harmonic Source Location Method Based on PMU Measurements in Distribution Network

Bing Jun Li,Su Quan Zhou,Xiao Xiang Lun
DOI: https://doi.org/10.4028/www.scientific.net/amm.775.409
2015-01-01
Applied Mechanics and Materials
Abstract:It is of great importance to identify the location of the harmonic sources for the harmonic governance in the power system. Applied with optimal measurement placement (OMP) and harmonic state estimation (HSE), this paper presents a novel process based on PMU measurements to locate the harmonic sources in the distribution network. Considering the cost and the observability, the OMP can provide a scheme of the measurement placement with the minimum number of PMU measurements. In order to simplify the HSE equation, the measured data are converted to the form of voltage by the method proposed in this paper.By solving the HSE equation, the location and magnitude of the harmonic source are evaluated. The methodology is applied to the IEEE 33-bus system, and the obtained results are properly analyzed.
What problem does this paper attempt to address?