Dead-Beat Control Method for Shunt Active Power Filter and Application
WANG Xiao,SHUAI Zhikang,WANG Yichao,XIE Ning,JIAN Wan,WANG Yi
DOI: https://doi.org/10.3969/j.issn.1001-5531.2012.17.012
2012-01-01
Abstract:To compensate the harmonic of a smelter,in connection with the shunt active power filter,a mathematical model was built.With the model,the effect of the PI parameter on the stability of closed-loop system was analyzed based on the bode features of the PI transfer function.Compared with the traditional PI control method,this paper put forward an inner current loop composite correction dead-beat control method,giving the simulation analysis in the systematic responsiveness and the control accuracy,and proposing the pulse width modulation for this control system.Finally,an experimental platform was built for verification.The results show that,with the dead-beat control method,the stability and reliability of this system are improved greatly.Its good compensation performance shows that the proposed control method is feasible in both theory or practice.