Technical Feasibility of A Stratum-Ventilated Room for Multiple Rows of Occupants

Yong Cheng,Zhang Lin
DOI: https://doi.org/10.1016/j.buildenv.2015.10.015
IF: 7.093
2015-01-01
Building and Environment
Abstract:This study aimed to explore the technical feasibility of stratum ventilation for a room with occupants in multiple rows. Theoretical analysis, human subject tests and computational fluid dynamics (CFD) simulations were conducted. All the results showed that stratum ventilation can be used for a room with multiple rows of occupants. Human subject tests indicated that the acceptable thermal comfort with low draft was achieved for the two rows of occupants. The CFD simulations showed that the acceptable thermal comfort level has been reached, measured by EDTS (effective draft temperature for stratum ventilation), PMV (predicted mean vote), PPD (predicted percentage dissatisfied) and PD (percentage dissatisfied due to draft), and air of young age was also achieved for the three rows of occupants. This is because the cool fresh supply air can flow around and over the front-row occupants to reach the back rows even though they establish a local blocking effect to the supply airflows. Thus, the number of rows should not be a decisive factor for stratum ventilation. Therefore, it is reasonable to expect that with properly designed air supply parameters, stratum ventilation can be applied in a room with multiple rows of occupants.
What problem does this paper attempt to address?