Heat loss analysis of a 10kA warm dielectric HTS DC cable

shaotao dai,liye xiao,yuping teng,naihao song,zhiyuan gao,zhiqing zhu,xueming liang,zhicheng cao,dong zhang,tao ma,hongen zhang,liangzhen lin
DOI: https://doi.org/10.1016/j.cryogenics.2014.05.008
IF: 2.134
2014-01-01
Cryogenics
Abstract:•A 10kA HTS power cable has been demonstrated, both the cable and its supporting system are introduced.•The structure and its heat losses of the 10kA HTS cable system are discussed in detail.•A dual vacuum layer insertion technology is developed to connect the cryogenic envelope segment of the cable.•The termination and cryogenic envelope are the main heat loss sources of the cable.•The actual power consumption for the 1698W of the HTS cable is 39kW, 48% of that consumed by the aluminum bus.
What problem does this paper attempt to address?